Fire-Lite FCPS Series Field Charger/Power Supply User Manual

Page 34

Advertising
background image

34

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

Applications

Remote Supply With Resettable and Nonresettable Power

For addressable panel applications, an addressable monitor module can be used to monitor the trou-
ble contact of the FCPS-24FS and the resettable power connection from the FACP using an End-of-
Line power supervision relay. If the FCPS-24FS enters a trouble condition, the Normally Closed
trouble contact will open and if the resettable power from the FACP is lost, the Normally Closed
power supervision relay contact will open.

The following notes apply to Figure 5.4 on page 34.

1. An End-of-Line Resistor must be installed between TB5, Terminal 1 (trouble relay common)

and the monitor module input circuit for module wiring supervision (the ELR value is
dependent on the module employed).

2. An End-of-Line power supervision relay must be connected between TB4, Terminals 5 & 6.

The Normally Closed (when energized) power supervision relay contact must be in series with
the End-of-Line Resistor referred to in note 1.

3. Do not loop wires under screw terminals. Break wires to maintain proper supervision.
4. For a list of compatible devices, refer to the Fire•Lite Device Compatibility Document #15384.

Figure 5.4 Remote Power Supply Application

Power Output 1
Resettable

Power Output 2
Resettable

Power Output 3
Nonresettable

Power Output 4
Nonresettable

SLC

SLC

Monitor Module*

FACP

24 VDC

Resettable

Power

FCPS-24FS

EOL Power

Supervision

Relay

EOLR-1

(energized)

SW1 Switch Settings
1 = OFF
2 = OFF
3 = OFF (master)
4 = ON (Aux Trouble Relay responds
to all troubles)
5 = OFF
6 = ON
7 = OFF (charger enabled)
8 = OFF (circuit 4 NAC)

Split Alarm

No Sync

End-of-Line Resistor supplied
with Monitor Module

24

fs

ap

p4

tp

H.

wm

f

*If the SLC device does
not match the one in this
figure, refer to the SLC
manual wiring conversion
charts for legacy and newer
versions of the modules.

T11
T10
T9
T8
T7
T6

T1
T2
T3
T4
T5

Advertising