Fire-Lite FCPS Series Field Charger/Power Supply User Manual

Page 28

Advertising
background image

28

FCPS-24FS Series Instruction Manual — P/N 51883-L8:J1 8/30/13

Applications

Controlling Four NACs With One Input and Selective Silence

The control module is shown to demonstrate the use of a remotely mounted device associated with
an addressable fire alarm control panel. The module could be replaced with any circuit capable of
polarity reversal, such as an FACP NAC.

The following notes apply to Figure 5.1 on page 28.

1. When the FCPS-24FS power supply is in an inactive state (control module not active), a

trouble on the power supply will result in an open circuit condition on the control module
output circuit (monitored by End-of-Line Resistor across TB4, Terminals 5 & 6). As an
alternative, the trouble contacts at TB5 of the power supply can also be used for independent
trouble monitoring.

2. The addressable relay module must be programmed as a silenceable point at the FACP to allow

selective silence of horn/strobe devices. The Normally Open contact of the relay module is
connected between TB4 Terminal 7 (IN2 +) and Terminal 9 (Aux. Power +).

3. Do not loop wires under screw terminals. Break wires to maintain proper supervision.
4. An End-of-Line Resistor must be installed between TB4, Terminals 5 & 6 for control module

wiring supervision (the ELR value is dependent on the module employed).

Figure 5.1 Controlling Four Outputs With One Input

Control Module*

Relay Module*

EOL Power

Supervision Relay

EOLR-1

(energized)

SLC

SLC

Style Z (Class A)

Style Y (Class B)

Use listed ELR
(4.7K

Ω) to terminate

Style Y (Class B)
NAC

Note: All NACs are supervised and power-limited (Class 2)

ZNAC-4

Option Module

Output/NAC 4

Output/NAC 3

Output/NAC 2

Output/NAC 1

FCPS-24FS has been set for
Selective Silence and Relay
Module has been programmed
at FACP as a silenceable point
so it can perform selective
silence when its Normally Open
contact (8 & 10) closes in
alarm, then opens when silence
is invoked at the FACP.
Note: the Relay Module can be
mounted on the power supply
inside the cabinet. This allows
power wiring to remain inside
the cabinet.

SW1 Switch Settings

1 & 2 = sync (any setting but OFF/OFF)

3 = OFF (master)

4 = OFF (no AC Fail reporting delay)

5 = ON

6 = ON

7 = OFF (charger enabled)

8 = OFF (circuit 4 NAC function)

(selective silence)

End-of-Line Resistor
supplied with Control
Module

Internal Trouble Contact

ELR not required for
Style Z (Class A) NAC

FCPS-24FS

Horn/Strobes

Alarm Polarity Shown

Horn/Strobes

Alarm Polarity Shown

24f

sapp

7

tp

H

.w

m

f

*If the SLC device does not match the one in this figure,
refer to the SLC manual wiring conversion charts for
legacy and newer versions of the modules.

T11

T10

T9

T8

T7

T6

T11

T10

T9

T8

T7

T6

T1

T2

T3

T4

T5

T1

T2

T3

T4

T5