2) (see, Nac (notification appliance circuits) – Fire-Lite PS-Tools MS-9050 User Manual

Page 38

Advertising
background image

30

50 Pt Addr Panel

PS-Tools

08/2010

Configuring Fire Panels

NAC (Notification Appliance Circuits)

The notification appliances include speakers, horns, strobes, bells, and other type of sounder
appliances. There are four notification appliance circuits, which can be configured for the 50 Pt Addr
panel.

Figure 5-4

Configuring Notification Appliance Circuits

To configure NAC 1

1.

Click NAC 1 Enabled, to enable NAC 1, If you select Disable, the fire panel prevents the
selected NAC from activating its devices.

2.

Click NAC 1 - 1 Minute Silence Inhibit Enabled, to enable the silencing of the audible
devices in NAC 1, only after 60 seconds. If this option is enabled, the audible devices can be
silenced by pressing the Alarm Silence key, only after 60 seconds.

3.

Click NAC 1 - Silenceable, to indicate if the notification appliance can be silenced by pressing
the Alarm Silence key. If the Silenceable option is not enabled, the selected NACs cannot be
silenced by pressing the Alarm Silence key or by the Auto Silence feature.

4.

Select the delay for NAC 1 Auto Silence from the list, to automatically silence the main circuit
board silenceable NACs after a programmed length of time. This option is disabled if the
Silenceable option is not selected.

5.

Select the NAC 1 Coding option to specify the type of output the main circuit board
notification appliances generates, when activated. For more information about each coding
selection, see

Appendix

.

6.

Select the NAC 1 Type Code from the list.