As in, Table 5-1, Loop style – Fire-Lite PS-Tools MS-9050 User Manual

Page 42

Advertising
background image

34

50 Pt Addr Panel

PS-Tools

08/2010

Configuring Fire Panels

Note

If the Canadian option is enabled, then the silence inhibit for NACs becomes a
“global” option. That is, in the panel if you change any NAC to silence inhibit, the
remaining NACs change to silence inhibit. Similarly, if you set any one NAC to
no silence inhibit all the NACs silence inhibit is turned off.

When importing a customer database file from the previous version of PS-Tools,
a check must be performed to ensure whether the Canadian option is enabled. If
the Canadian option is enabled, then the NAC’s silence inhibit must be checked.
If either of them is enabled, then all the NAC’s silence inhibit must be turned off,
and a corresponding message must be displayed to the user.

If Canadian option is ON, then the PAS and Pre-signal timers must be set to 0 and
no editing is allowed.

If Canadian option is ON, then the secondary Ann Bus must be enabled. You can
toggle between the secondary Ann Bus enable and disable option.

Table 5-1

Module types blocked from selection

Changes to

Monitor

Pull Station

MON User defined 3

Pull Station

Medical Alert, Hazard Alert, and Tornado Alert

Supervisory

Supervisory AR (Non-Latching)

Supervisory

MON User defined 7, 8, 9, 13, 16, and 17

Supervisory

Drill Switch AR (Non-Latching)

Drill Switch

Process Monitor AR and Process Monitor

Supervisory

Module and Zone types available for Canadian option

Loop Style

Under Loop Style, select the Loop 1 Style, for the loop. The wiring style can be Style 4 or Style 6.
The default wiring type is Style 4.

Zone types blocked from selection

Changes to

AR(auto-resettable) Supervisory

Supervisory

Drill Switch AR

Drill Switch

Process monitor, hazard, tornado, and medical alert

Supervisory