Fire-Lite PS-Tools MS-9050 User Manual

Page 56

Advertising
background image

48

50 Pt Addr Panel

PS-Tools

08/2010

Configuring Fire Panels

2.

Under Device Address, click Loop 1 and specify the device Address which is a three digit
value between 01 to 50.

3.

To add only one module, click Single Device.

4.

To add more than one module, click Multiple Devices.

5.

Specify the number of modules you want to add in No. of devices.

6.

Select the Device Type from the list.

7.

To add a user defined device type select USER-DEF-1 from the list and click Edit Custom
Type
. Type the new type label in the displayed window and click OK.

8.

In Device Label, select the Adjective and the Noun, which specify the module location. The
adjective and noun are specific descriptors to identify the module location. To add a custom
adjective/noun, select the Add New option from the adjective/noun list and specify the custom
adjective/noun in the displayed window. Custom Label displays the selected Adjective and
Noun.

9.

In Device Options, the Device Enabled option is selected by default (when you click Add
Device). If this option is not selected, the module is not polled by the control panel, which
prevents the module from reporting alarms and troubles to the panel. The control panel displays
the device type and address of the device disabled and activates the Trouble and Disable LEDs.

10. To enable the Pre-Signal option for a module, click Pre-Signal Enabled option. The Pre-signal

option programs the module to delay panel activation for a preprogrammed time delay of up to
three minutes while allowing for visual verification.