PS-Tools User Guide

50 Pt Addr Panel

PS-Tools

08/2010

39

ANN-Bus Address

ANN-Bus Address allows you to install the modules type in their respective 1-8 addresses.

To configure the ANN-Bus Address

1.

Under Primary ANN Bus Address, select the Module Type for each address. (see

Figure 5-7

).

2.

Click Next or click Detectors in the left pane, to configure the detectors.

SLC Loop Setup

SLC loops provide communication to addressable detectors, monitor (initiating device), and control
(output device) modules. One SLC loop is provided by default on the fire panel main circuit board.
You can plug the optional SLC module into the connector, on the main circuit board for the second
SLC loop. The 50 Pt Addr fire panel addressable device capacity is 50 which is the sum of detectors
and control/monitor modules per SLC loop.

You can configure the SLC Loop for NFPA Style 4, 6, or 7. The wiring styles Style 4 or Style 6 are
mostly used. Style 7 wiring is same as Style 6 with the added requirement that each addressable
device on the loop must have a pair of isolator modules, one on each side. To program a system for
Style 7, you must select the loop setup for Style 6. You can configure all the addressable devices to
SLC Loop 1, in the SLC Loop Setup screen.

Detectors

The SLC Loop Setup > Detectors pane helps you to perform the following:

View the added detector in a tabular or graphical form.

Add a new addressable detector to an SLC loop.

Change the programming for an existing detector.

Delete an existing detector from a loop.

Search for detector in a zone.