HT instruments HT7051 User Manual

Page 12

Advertising
background image

HT2055

EN - 11

5.1.4 Default

settings

This section permits to restore the default value (factory) of measurement parameters and
limits set on the instrument

Fig. 10: Initial settings screen

1. Press

or

keys to enter Settings menu

2. Select the item “Initial Settings” with the  or  keys and press TEST key
3. Select the “NO” or “YES” options with the  or  keys and confirm with TEST
4. Press ESC key to exit and go back to the previous screen

The default values are the following:

Language

English

Contact and Step voltage

I

GEN

= 10A

I

FLT

= 1kA

R

INP

= 1MΩ

U

LIM

= 50V

5.1.5 Time/Date

settings

Fig. 11: Time/Date settings screen

1. Press

or

keys to enter Settings menu

2. Select the item “Set Date/Time” with the  or  keys and press TEST key
3. Use the ,, and  keys to set the date/time and confirm with TEST
4. Press ESC key to exit and go back to the previous screen

5.2 MESSAGES AT DISPLAY
The below messages (icons) can be displayed on the meter unit:

The meter and the station are not synchronized

Measurement is running

Results can be stored

Measurement result is within pre-set limits (PASSED)

Measurement result is out of pre-set limits (FAILED)