11 TECHNICAL SPECIFICATIONS

The accuracy is calculated as [% rdg + (number of dgt) * resolution] at reference condition
indicated in § 11.2

Step/Contact voltage measurement

Measured voltage range

Resolution

Accuracy

0.01

 19.99mV

0.01mV

(2.0rdg + 2dgt)

20.0

 199.9mV

0.1mV

200

 1999mV

1mV

2.00

 19.99V

0.01V

20.0

 59.9V

0.1V

Calculated voltage range

Resolution

Accuracy

0.0

 199.9V

0.1V

calculated value (*)

200

 999V

1V

(*) The calculated value of step/contact voltage is obtained by the relationship: U

S

=U

mis

·

I

flt

/I

gen

;

U

C

=U

mis

·

I

flt

/I

gen

;

Fault current range (selectable):

10A

 200kA

Input resistance (selectable):

1k

, 1M

Noise reducing:

DSP 55Hz filtering, 64dB rejection of 50/60Hz noise

Generated current range

Resolution

Accuracy

0.00

 9.99A

0.01A

(3.0rdg + 5dgt)

10.0

 99.9A

0.1A

(3.0rdg + 3dgt)

Generated current:

55A max

Test voltage:

<55V

Test frequency:

55Hz


Earth resistance measurement

Measurement range

Resolution

Accuracy

0.001

  1.999 0.001

(2.0rdg + 5dgt)

2.00

  19.99 0.01

20.0

  99.9

0.1

100.0

  199.9

(5.0rdg)

Open voltage:

< 50V AC

Test current:

< 7.5A

Frequency of test signal:

55Hz

Influence of probe resistance:

 ±(10%rdg + 10dgt)

(Rc, Rp)

max

(10

 + 100R) or 2k considering lower value

Automatic test of probe resistance:

Yes

Automatic detection of voltage noise

Ground resistivity measurement

Measurement range

Resolution

Accuracy

0.00

m  9.99m 0.01m

Calculated value, considering

accuracy of resistance to earth

function

10.0

m  99.9m 0.1m

100

m  999m 1m

1.00k

m  9.99km 0.01km

10.0k

m  99.9km 0.1km

Principle of measure:

Wenner method 