Synchronization between the units after the test (recommended)

If the meter and station units were synchronized during the measurements they should be
synchronized again after completing the tests. In this step the values of generated currents
(measured with the station) are downloaded to the meter so automatically correcting the
measured results previously stored and providing the correct value of step and contact
voltages.

14 Connect both meter and station units through the PS/2-RS-232 cable supplied (see

Fig. 20)

15 Select the option “Synchronize  Time, Current” on the meter unit (see § 5.1.3) and

confirm with TEST key. The messages “Connecting...” and Synchronizing… are
displayed.

16 The following screens can be displayed by the meter unit during the synchronization

Fig. 23: Example of screens on the synchronization operation

NOT SYNCHRONIZED  number of not synchronized results

CAUTION

Synchronization of step/contact voltage results can last up to several 10
seconds. A bargraph is showing the progress.