HT instruments HT7051 User Manual

Page 20

Advertising
background image

HT2055

EN - 19


Perform step/contact voltage measurements

8 Use

or

keys and select the CONTACT VOLT or STEP VOLT measurements

on the meter unit

Fig. 21: Screens for step/contact voltage measurements

9 Use

,, and  keys and perform the settings of the following test parameters:

Igen

Test current (manual setting considering the range 0.20A ÷ 50A) or
automatically fitted by the station unit during the synchronization

Iflt

Maximum fault current of earth system (range 10A ÷ 200kA)

Rinp

Input resistance of the meter unit (1M

, 1k)

Ulim

Limit value for step/contact voltage measurements (range 1V ÷ 10kV)


Iflt  Fault current value given by the Mains Energy provider
Rinp  Input resistance fixed to 1k

 for step/contact voltage measurements

Ulim  Voltage limit given by Guidelines according to the time of fault elimination by the
protection devices

10 Place and connect the test metal plates to each other where the operator stands, close

to the points where step voltage measurement (see Fig. 17) or contact voltage (see
Fig. 18) is required respecting the necessary distances


11 Connect the metal plates to the meter unit by using the cables supplied

12 Press TEST key on the meter unit and perform the step voltage of the contact voltage

measurements. The following screens are displayed by the meter:

Fig. 22: Screens for results of step/contact voltage measurements

Where:

U  calculated step/contact voltage
Um  measured step/contact voltage

13 Press MEM key to save the result inside memory (see § 8.1)