Caution – HT instruments HT7051 User Manual

Page 23

Advertising
background image

HT2055

EN - 22



5 Use

or

keys and select the EARTH RE measurement on the station unit. The

following screen is displayed:

Fig. 25: Main screen of earth resistance measurement

6 Press

TEST

key to perform the measurement. The result is displayed

Fig. 26: Result screen of earth resistance measurement


Where:

R  Measured value of earth resistance
Rp  Voltage probe resistance (S)
Rc  Current probe resistance (H)

CAUTION

 When starting test the unit performs a preliminary check of the resistance

values for current probe (Rc) and voltage probe (Rp) stopping the test if
these values are assumed to be too high and giving the following
messages “Rc: >2.0k

” and “Rp: >2.0k”. Decrease the value of these

resistance wetting the ground close to the probes and/or connect more
probes in parallel

 High noise currents and voltages on earth could affect the measurement

results. In this case the tester displays the ”NOISE” warning



7 Press

MEM

key to save the result inside memory (see § 8.1)

CAUTION

To view stored earth resistance results on PC they must be downloaded to the
meter unit first. To download the results select earth results from Synchronize
menu (see § 5.1.3). After the results are downloaded the stored data in
the station unit will be automatically deleted



Advertising
This manual is related to the following products: