background image

HT4020 - HT4022

EN - 10

4.3.3. Measurement of Voltage Harmonics (HT4022)

CAUTION

 The maximum Voltage input is 600V. Do not attempt to take any voltage

measurements exceeding the limits indicated in this manual. Exceeding
the limits could cause electrical shock or damage to the instrument.

 Harmonic voltage measure is active for AC voltage on inputs only.

Fig. 6: Use of instrument for AC voltage harmonic measurement


1. Select the “

V

” position

2. Press FUNC/HARM key and keep it pressed at least 1 second until symbol “THD%

is displayed

3. Insert the red plug into V/

 jack and the black plug COM into jack. For ease of use,

attach the rubber test lead holster and insert a test lead (see Fig. 3)

4. Connect the test leads to the circuit under test (see Fig. 6). The instrument displays the

Total Harmonic Distortion value of the input signal. The symbol “THD%” is shown on
the display. See § 8 for the parameter’s definition

5. With the H

 and H keys you can cycle through all available harmonic values from DC

to the 25

th

order. On the secondary display is shown the order of the harmonic whose

percentage value is displayed on the main one (ex. h3% means third harmonic)

6. Press the FUNC key to switch to the absolute harmonics’ values displaying (from

DC to 25

th

order). On the secondary display is shown the order of the harmonic whose

absolute value is displayed on the main one (ex. h3 means third harmonic)

7. Press FUNC key to escape this mode going back to voltage measurement function

(see § 4.3.1)