HT4020 - HT4022

EN - 20

6. Press the FUNC key, the “MEASURING” symbol will disappear.
7. Disconnect the test lead from the first 3-phase system . The symbol “2PH” appears on

the secondary display

8. Connect the test lead to the L1 phase of the second 3-phase system (see Fig. 14 –

right part)

9. When an input voltage >80V is detected the buzzer sounds and the symbol “PH” is

shown on the main display. Don’t press any key and keep the test lead connected to L1
phase cable.

CAUTION

If the input voltage value is < 80V the instrument doesn’t show “PH” symbol
and it’s not possible to execute the phase rotation detection.


10. After about one second “MEASURING“ appears indicating the instrument is ready to

execute the second measurement.

11. Press the

FUNC key, the “MEASURING” symbol disappears.

CAUTION

If you Wait more than 10 seconds between the first

FUNC key press and

the second, the instrument will display the “SEC” message and it’s
necessary to repeat all the measurements from the beginning. Rotate the
selector to any position to escape the function and restart at step 1.


12. If the two test cables belong to the same phase, the instrument displays “1.1.-.”,

otherwise it displays “2.1.3.” or “1.2.3.” This indicates that the two cables belong to two
different phases

CAUTION

 The detected voltage is NOT the phase to neutral voltage, but the

voltage between the conductor and the operator who is holding the
instrument. This value can be lower than the phase to neutral voltage.
DON’T TOUCH THE PHASE CABLE IF YOU AREN’T SURE THAT
ANY VOLTAGE IS PRESENT
.

 If the operator is insulated from the ground (e.g. insulated floors, shoes

with thick rubber, etc.) the instrument may not measure correctly. We
recommend repeating test at least twice due to verify the rightness of the
obtained result.