M-4102A

By applying the Voltage (V) to the circuit from the Transformer jaw (CT1), current I

is (shall be flowed) flowed corresponding to the earth resistance. R can be put out

by the calculation after detecting the current with the other Transformer jaw (CT2).

In this case, R displayed in this instrument can be regarded as Rx because Rs can

be regarded small enough against Rx.

#

CAUTION

This instrument is not supporting the measurement for the locations with

following earth systems.

Single-earth that is not connected to other earths. (Lightning rod, etc.)

Earth on which a current over 2A is measured at AC current function of this

instrument.

Earth with a larger earth resistance than an earth resistance of testing.

Earth with earth resistance over 1200Ω.

Precision measurement shall be performed with our Earth resistance tester:

M-4102A or M-4105A for the measurement of single-earthed wire.