6. 17

MODEL6300

Section 6 Instantaneous value measurement

MODEL6300


6-5 Ranges and Over-range indication

6-5-1 Ranges

The settings determine the range for each measurement parameter, namely:

Voltage range (“Setting 02”), Current range (“Setting03”), VT ratio (“Setting
05”) and CT ratio (“Setting 06”). (Fixed range)

Ɣ Voltage V: V(average of each phase), V1/V2/V3 (each phase), max 4 digits

150/300/600V range

Voltage range x VT ratio x 120%

Digit & Decimal point position

180 ~ 999.9 V

999.9 V

1k ~ 9.999 kV

9.999 kV

10k ~ 99.99 kV

99.99 kV

100k ~ 999.9 kV

999.9 kV

1M ~

7.2 MV

7.200 MV

When the value of (Voltage range x VT ratio x 120%) exceeds 9999, the
decimal point moves one place to the right.

Ɣ Current A: A(average of each phase), A1/A2/A3 (each phase), max 4 digits

50A Clamp sensor

: 5 / 10 / 20 / 50A range

100AClamp sensor

: 10 / 20 / 50 / 100A range

200AClamp sensor

: 20 / 50 / 100 / 200A range

500AClamp sensor

: 50 / 100 / 200 / 500A range

1000AClamp sensor : 100 / 200 / 500 / 1000A range
3000AClamp sensor : 1000 / 3000A range

Current range x CT ratio x 120%

Digit & Decimal point position

6 ~ 9.999 A

9.999 A

10 ~ 99.99 A

99.99 A

100 ~ 999.9 A

999.9 A

1k ~ 9.999 kA

9.999 kA

10k ~ 99.99 kA

99.99 kA

100k ~ 999.9 kA

999.9 kA

1M ~ 9.999 MA

9.999 MA

12 MA

12.00 MA

When the value of (Current range x CT ratio x 120%) exceeds 9999, the
decimal point moves one place to the right.