Wiring

Series 642

10

Pyromation, Inc.

4.2

Connecting the sensor

4.3

Connecting the measuring unit

NOTICE

Electronic parts may be damaged
► Switch off power supply before installing or connecting the device. Failure to observe this may

result in destruction of parts of the electronics.

► If the device has not been grounded as a result of the housing being installed, grounding it via

one of the ground screws is recommended.

4.3.1

HART

®

connection

Connection using a transmitter power supply

HART

®

connection with a transmitter power supply

Please refer to Section 4.1 "Quick wiring guide" for the terminal assignment of the sensor
connections.

If the HART

®

communication resistance is not built into the power supply, a 250

Ω

communication resistor must be fitted into the 2-wire supply lines.
For connection hints, please take special notice of the documentation supplied by the
HART

®

Communication Foundation, specifically HCF LIT 20: “HART, a technical

overview”.