4 screening and potential equalization, Screening and potential equalization – Pyromation Series 642 User Manual

Page 11

Advertising
background image

Series 642

Wiring

Pyromation, Inc.

11

Connection using other power supplies

HART

®

connection using other power supplies, e. g. a SPS

4.4

Screening and potential equalization

Please take note when installing the device:
If screened (shielded) cables are used then the screen connected to the output (output signal 4 to
20mA) must be at the same potential as the screen at the sensor connection!
When operating in plants with high electromagnetic fields, it is recommended that all cables be
screened using a low ohm ground connection. Due to the possible danger of lightning strikes
screening is also recommended for cables that are run outside buildings!

Advertising