Pyromation Series 642 User Manual

Page 21

Advertising
background image

Series 642

Commissioning

Pyromation, Inc.

21

Availability in TransComm Light, HART

®

communicator DXR375 (symbol

7

)

TransComm Light

7

Offset

Input of the zero point correction (offset).
Input: -10.00 to 10.00 °C (-18.00 to 18.00 °F)
0.00 °C

+

+

Unit

Display of measurement unit.
Sensor unit = PV unit

+

+

Serial no. sensor

Input of the serial number of the sensor connected to this sensor input.

+

+

Function group SENSOR

Function group OUTPUT

Availability in TransComm Light, HART

®

communicator DXR375 (symbol

7

)

TransComm Light

7

PV lower range value

Input of 4 mA value.
Input: Limitation values see device function SENSOR TYPE.
0 °C

+

+

PV upper range value

Input of 20 mA value.
Input: Limitation values see device function SENSOR TYPE.
100 °C

+

+

Analog output

Input of the standard (4 to 20 mA) or inverse (20 to 4 mA) current output signal.
Input:

4 to 20 mA
• 20 to 4 mA

+

+

Filter

Selection of the digital filter 1. order (filter time constant).
Input: 0 to 60 s

+

+

HART Output/
Multidrop

Preamble

Input: Number of response preambles: 5 to 20
5

-

+

Device
address

Input: HART address of the temperature transmitters:
0 to 15
If addresses > 0, the temperature transmitter
is in Multidrop mode and the analogue output is set to 4 mA. Device
address is shown on the display in the Multidrop mode