Pyromation Series 642 User Manual

Page 20

Advertising
background image

Commissioning

Series 642

20

Pyromation, Inc.

Availability in TransComm Light, HART

®

communicator DXR375 (symbol

7

)

TransComm Light

7

Sensor type

Sensor type

TC Type B

TC Type C
TC Type D

TC Type E

TC Type J

TC Type K

TC Type L

TC Type N

TC Type R

TC Type S

TC Type T

TC Type U

10 to 400

Ω

10 to 2000

Ω

-20 to 100 mV

Meas. range

start

0 °C (32 °F)
0 °C (32 °F)
0 °C (32 °F)

-270 °C (-454 °F)
-210 °C (-346 °F)
-270 °C (-454 °F)
-200 °C (-328 °F)
-270 °C (-454 °F)

-50 °C (-58 °F)
-50 °C (-58 °F)

-270 °C (-454 °F)
-200 °C (-328 °F)

10

Ω

10

Ω

-20 mV

Meas. range

full scale value

1820 °C (3308 °F)
2320 °C (4208 °F)
2495 °C (4523 °F)
1000 °C (1832 °F)
1200 °C (2192 °F)

1372 °C (2501.6 °F)

900 °C (1652 °F)

1300 °C (2372 °F)

1768 °C (3214.4 °F)
1768 °C (3214.4 °F)

400 °C (752 °F)

600 °C (1112 °F)

400

Ω

2000

Ω

100 mV

min. range

500 K (900 °F)
500 K (900 °F)
500 K (900 °F)

50 K (90 °F)
50 K (90 °F)
50 K (90 °F)
50 K (90 °F)
50 K (90 °F)

500 K (900 °F)
500 K (900 °F)

50 K (90 °F)
50 K (90 °F)

10

Ω

100

Ω

5 mV

+

+

Specific linearization and sensor matching
Selecting the sensor types 'Callendar-van-Dusen' or 'Polynomial RTD' improves the accuracy of the system or defines user-specific linearisation of resistance
thermometers. A detailed description of the 'Callendar-van-Dusen' method and 'Polynomial RTD' linearisation is provided in the Appendix to these Operating
Instructions.

The selection list of the sensor type is displayed depending on the PV unit. Example: When
selecting a resistance thermometer the PV unit must first be set to

Ω.

Sensor connection

Input of RTD connection mode.
Input:

• 2-wire
3-wire
• 4-wire

Function is only active on selection of a resistance thermometers (RTD) in the device
function SENSOR TYPE.

+

+

Cold junction

Selection of the internal (Pt100) or an external comparison
measurement point.
Input:

internal
• external

Function is only active on selection of a thermo-couple (TC) in the device function SENSOR
TYPE.

+

+

External
temperature

Input of the external comparison point measurement value.
Input: -40.00 to 85.00 °C (°C, °F, K)
0 °C
Function is only active when "external" has been selected in the device function COLD
JUNCTION.

+

+

2-wire
compensation

Input of cable resistance compensation on a 2-wire RTD connection.
Input: 0.00 to 30.00

Ω

Function is only active when a 2-wire connection has been selected in the device function
SENSOR CONNECTION.

+

+

Function group SENSOR