23

• Display: PV (= Primary Value)
• Display: sensor value
• Display: RJ value
• Display Analogue output value
• Display: Status

• Display: percentage value (on/off)

The primary value (PV) is displayed as a
percentage.

(DXR=1)
(DXR=2)
(DXR=8)

(DXR=16)
(DXR=32)

off (DXR=0)

on (DXR=64)

+
+
+
+
+

+

+
+
+
+
+

+

In order to activate the values to be shown in the device display using HART

®

handheld

module DXR375: Add (DXR=x) of the values to be displayed and enter the sum.

• Display: time (2s, 4s, 6s, 8s)
• Display: figures after decimal point (0,1,2)
• Display PV text (customer specific text, 8 characters)

+
+
+

+
+
+

Function group DISPLAY

Function group DIAGNOSTICS

Availability in TransComm Light, HART

®

communicator DXR375 (symbol

7

)

TransComm Light

7

Diagnostics

Display of information required for device diagnostics.

• Device status or error code

(See chapter 9.2 "Error messages")

• Last error code (status) or previous error code

(See chapter 9.2 "Error messages")

• Status sensor (0 = no error; 0

≠ error)

• Configuration changed

+

+

-
+

+

+

+
+

Diagnostics

• Static revision

The "Static revision" is increased on every parameter change. This is for compliance to
21 CFR Part 11, showing that no further parameter changes have been made.

• Sensor max. value
• Sensor min. value
• RJ max. value
• RJ min. value

Display of the maximum process value. The process value will be accepted after starting
the measurement.
Display of the minimum process value. The process value will be accepted after starting
the measurement.
Display of the maximum and minimum measured temperatures of the internal Pt100 DIN
B comparison measurement point.

• Maximum process value is changed to the actual process value on write access. On

reset to factory default value the default value is entered -9999.99.

• Minimum process value is changed to the actual process value on write access. On

reset to factory default value the default value is entered +9999.99.

-

+
+
+
+

-

+
+
+
+

Function group IDENTIFICATION

Availability in TransComm Light, HART

®

communicator DXR375 (symbol

7

)

TransComm Light

7

Measuring point
Input and display of the information relating to the measuring point identification

Advertising