2 visual indicators, 3 output signals, 1 0-20ma current output – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 27: Visual indicators, Output signals, 20ma current output, Table 3: detector led indications, Table 4: source led indications

Advertising
background image

TM 888200 Rev (I), January 2014

Visual Indicators

15

3.2

Visual Indicators

One 3-color LED indicator is located in the back side of the detector/source
and can be seen through the back cover window. See Figure 2 and
Figure 3, item 11.

The detector statuses are listed in Table 3.

Table 3: Detector LED Indications

Detector Status

LED Color

LED Mode

Fault

Yellow

4Hz – flashing

Alignment / Standby

Yellow

1Hz – flashing

Zero Calibration

Yellow

Constant

Normal

Green

1Hz – flashing

Warning

Red

2Hz – flashing

Alarm

Red

Steady

The source statuses are listed in Table 4.

Table 4: Source LED Indications

Source Status

LED Color

LED Mode

Fault

Yellow

4Hz – flashing

Normal

Green

1Hz – flashing

3.3

Output Signals

The SafEye system provides the following outputs:

0-20mA Current Output, page 15

RS-485 Interface, page 16

3.3.1 0-20mA Current Output

The 0-20mA output provides the detector status measurement showing a
continuous reading of exact gas concentration.

The 0-20mA functions as current sink, but it can be configured as Source
(see Appendix A).

The maximum permitted load resistance for the 0-20mA output is 600Ω.

Advertising