2 electrical specifications, 1 power consumption, 2 electrical input protection – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 32: 3 electrical outputs, 1 0-20ma current output, 2 communication network, 3 hart protocol, Electrical specifications, Power consumption, Electrical input protection

Advertising
background image

SafEye

TM

Quasar 900 Gas Detector

20

Electrical Specifications

Immunity to false
alarm:

Does not produce false alarm and is not
influenced by Solar Radiation, Hydrocarbon
Flames and other external IR Radiation Sources.

4.2

Electrical Specifications

Operating Voltage:

18-32 VDC

4.2.1 Power Consumption

Table 9: Detector and Source Maximum Power Consumption

Without Heated
Optic (Max.)

With Heated
Optic (Max.)

Detector

200mA

250mA

Source

200mA

250mA

4.2.2 Electrical input protection

The input circuit is protected against voltage-reversed polarity, voltage
transients, surges and spikes according to EN50270.

4.2.3 Electrical outputs

4.2.3.1 0-20mA Current Output

The 0-20mA is isolated sink option. This output can be configured as Source
(see Appendix A).

The maximum permitted load resistance is 600 ohm.

4.2.3.2 Communication Network

The Detector is equipped with an RS 485-communication link that can be
used in installations with computerized controllers.

Communication is compatible with the Modbus protocol:

This protocol is a standard and is widely used.

It enables continuous communication between a single standard Modbus
controller (Master device) and a serial Network of up to 247 Detectors.

It enables connection between different types of Spectrex Detectors or
other Modbus devices to the same Network.

4.2.3.3 HART Protocol

The HART Protocol is a digital communication signal at low level on top of
the 0-20mA.

This is a bi-directional field communications protocol used to communicate
between intelligent field instruments and the Host System.

Advertising