8 detector terminal wiring, 9 flash source wiring, 1 wiring – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 46: Detector terminal wiring, Flash source wiring, Wiring, Table 11: wiring options

Advertising
background image

SafEye

TM

Quasar 900 Gas Detector

34

Detector Terminal Wiring

5.8

Detector Terminal Wiring

The Detector has six wiring terminals.

The following describes the function of each electrical terminal of the
detectors.

Table 11: Wiring Options

Terminal

No.

Function

1

Power +24V DC

2

Return +24V DC

3

0-20mA (Input)

4

0-20mA (Output)

5

RS-485 (+)

6

RS-485 (-)

5.9

Flash Source Wiring

5.9.1 Wiring

To install the wiring:

1

Release the back screw bolt (item 15, Figure 5), and open the source
back cover (item 14, fig. 4). The chamber is now revealed.

2

Remove the protective plug mounted on the source conduit/cable entry
inlet; pull the wires through the source inlet (item 4, Figure 7). Use a
3/4” – 14NPT or M25x1.5 explosion-proof conduit connection / cable
gland to assemble the cable / explosion-proof conduit to the Detector.

3

Connect the wires to the required terminals (item 2, Figure 7) according
to the wiring diagram. See paragraph Terminal Wiring, page 35 and
Figure 11 Appendix A.

4

Connect the grounding wire to the ground screw outside Detector
(item 3, Figure 7). The source must be well grounded to Earth Ground.

5

Place and secure the source back cover by screwing the cover and
secure the back screw bolt.

Advertising