Rs-485 communication network, Figure 14: rs-485 networking for wiring option 3, A.1 rs-485 communication network – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 65

Advertising
background image

TM 888200 Rev (I), January 2014

RS-485 Communication Network

53

A.1

RS-485 Communication Network

By using the RS-485 network capability of the SafEye Quasar 900 detector
and additional software, it is possible to connect up to 32 Detectors in an
addressable system with four (4) wires only (2 for power and 2 for
communication). Using repeaters, the number of Detectors can be much
larger (32 Detectors for each repeater) up to 247 on the same four (4)
wires. When using the RS-485 network, it is possible to read each Detector
status (FAULT, WARNING, and ALARM).

For more details, consult the factory.

Figure 14: RS-485 Networking for Wiring Option 3

Advertising