3 mechanical specifications, Mechanical specifications – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 33

Advertising
background image

TM 888200 Rev (I), January 2014

Mechanical Specifications

21

Through the HART Protocol the detector can:

Display set-up

Reconfigure set-up

Display detector status and definition

Perform detector diagnostic

Troubleshooting

4.3

Mechanical Specifications

Enclosure:

The Detector, Source and tilt mount are St. St. 316
Electro chemical and passivized coating.

Explosion Proof: ATEX &

IECEx

EX II 2 GD,
Ex d e ib [ib Gb] IIB+H2 T4 Gb
Ex tb IIIC T135°C Db IP66

FM/FMC

Class I Div. 1 Groups B, C, and D
Class II/III Div. 1 Groups E, F, and G
T6 -58°F (-50°C) ≤ Ta ≤ 149°F (65°C)

Functional
Testing:

Approved per FM 6325
Tested by FM per EN60079-29-4

Water and Dust
Tight:

IP 66 and IP 68
IP68 is rated for 2 meter depth for 45 minutes.
NEMA 250 type 6p

Electrical
Modules:

Conformal coated

Electrical
Connection:

(Two options - specified at time of order)
2 X M25 (ISO)
2 X 3/4” - 14NPT conduits

Dimensions:

Detector 10.5 x 5.1 x 5.1 in (267 x 130 x 130mm)
Source

10.5 x 5.1 x 5.1 in (267 x 130 x 130mm)

Tilt Mount 4.7 x 4.7 x 5.5 in

(120 x 120 x 40mm)

Weight:

Detector 11 lb

(5 kg)

Source

11 lb

(5 kg)

Tilt Mount 4.2 lb

(1.9 kg)

Advertising