General conditions for safe use, C.2 general conditions for safe use – Spectrex Quasar 900 Open-Path Gas Detection System User Manual

Page 70

Advertising
background image

SafEye

TM

Quasar 900 Gas Detector

58

General Conditions for Safe Use

C.2

General Conditions for Safe Use

The SafEye Quasar 900 IR Open-Path Gas Detector shall consist only of
the approved hardware and software modules.

The application advice and the limitations of the manual must be taken
into consideration. For calibration and maintenance, the regional and
national regulations have to be taken into consideration.

The 24V power supply must fulfill the requirements for PELV / SELV of
EN 60950.

The HART and RS 485 interfaces are not allowed to be used for the
transmission of safety related data.

The alert conditions according to SIL-2 can be implemented by an Alert
signal via the 20mA current loop.

After installation and configuration the set-up parameters must be
verified and the function of the SafEye Quasar 900 IR Open-Path Gas
Detector must be checked completely.

The alarm conditions of the transmitter must be checked periodically
together with the typical gas calibration checks. The SafEye Quasar 900
IR Open-Path Gas Detector must be switched OFF and ON.

The connected controller must monitor the 4-20mA signal current for
values below 4mA and above 20mA.

A defect on the SafEye Quasar 900 IR Open-Path Gas Detector must be
repaired within 72 hours.

Advertising