2 electrical specifications, 1 power consumption, 2 electrical input protection – Spectrex Xenon 700 SIL Open-Path Gas Detection System User Manual

Page 36: 3 electrical interface, 4 electrical outputs, 1 0-20ma current output, 2 communication network, Electrical specifications, Power consumption, Electrical input protection

Advertising
background image

SafEye

TM

Xenon 700S SIL Gas Detector

24

Electrical Specifications

4.2

Electrical Specifications

Operating Voltage:

18-32 VDC

4.2.1 Power Consumption

Table 12: Detector and Source Maximum Power Consumption

Without Heated
Optic (Max.)

With Heated
Optic (Max.)

Detector

220mA

300mA

Source

220mA

300mA

4.2.2 Electrical Input Protection

The input circuit is protected against voltage-reversed polarity, voltage
transients, surges and spikes according to MIL-STD-1275B.

4.2.3 Electrical Interface

There are three output-wiring options. These options must be defined at
factory per the customer order. See Appendix B for wiring/terminal diagram
for each option.

Note: Option 3 is the default unless otherwise specified at time of order.

Option 1:Power, Alarm Fault Relay, 0-20mA (Figure 9).

Option 2:Power, Alarm, Fault & Accessory Relay(Figure 10)

Option 3: Power, Alarm Relay, RS 485, 0-20mA, RS-485 RTN (Figure 11)

Note: SIL2 covers only 0-20mA outputs.

4.2.4 Electrical outputs

4.2.4.1 0-20mA Current Output

The 0-20mA is isolated sink option. This output can be configured as Source
– see Appendix B.

The maximum permitted load resistance is 600 ohm.

Two 0-20mA options:

Continuous reading – default (see Table 2)

Discrete reading (see Table 3)

4.2.4.2 Communication Network

The Detector is equipped with an RS-485 communication link that can be
used in installations with computerized controllers.

Communication is compatible with the Modbus protocol:

This protocol is a standard and is widely used.

Advertising