A wire selection tables, Wire selection tables, General instructions for electrical wiring – Spectrex Xenon 700 SIL Open-Path Gas Detection System User Manual

Page 65: Awire selection tables, A.1 general instructions for electrical wiring

Advertising
background image

General Instructions For Electrical Wiring

53

A

Wire Selection Tables

In this appendix…

General Instructions For Electrical Wiring

page 53

A.1

General Instructions For Electrical Wiring

Refer to Table 22 to determine the required wire gauge for general wiring,
such as relay wiring. Calculate the permitted voltage fall with respect to
loads current, wire gauge and length of wires.

Refer to Table 23 to select wire gauge for power supply wires. DO NOT
connect any circuit or load to Detectors’ supply inputs.

Table 22: Maximum DC resistance at 68˚F for copper wire

AWG #

mm

2

Ohm per 100 ft.

Ohm/100 meter

26

0.12 - 0.15

4.32

14.15

24

0.16 - 0.24

3.42

11.22

22

0.30 - 0.38

1.71

5.60

20

0.51 - 0.61

1.07

3.50

18

0.81 - 0.96

0.67

2.20

16

1.22 - 1.43

0.43

1.40

14

1.94 - 2.28

0.27

0.88

12

3.09 - 3.40

0.17

0.55

10

4.56 - 6.64

0.11

0.35

1

Select "Number of Detectors" connected in one circuit.

2

Select "wiring length" per your installation requirements.

3

Refer to "power supply range" for voltage extreme applied.

Advertising