8 troubleshooting, 1 troubleshooting problems, Troubleshooting – Spectrex Xenon 700 SIL Open-Path Gas Detection System User Manual

Page 61: Troubleshooting problems, Table 21: troubleshooting problems, 8troubleshooting

Advertising
background image

Troubleshooting Problems

49

8

Troubleshooting

In this chapter…

Troubleshooting Problems

page 49

8.1

Troubleshooting Problems

Table 21: Troubleshooting Problems

Problem

Cause

Solution

“Maintenance call”
status or R, S1 and
S2 are below 2.5V DC

at Gain 4

Poor alignment

Perform alignment

Dirt on the
window

Clean the window

Poor light source Replace the light source
Detector fault

Replace/repair Detector

NQRat1 and NQRat2
below the permitted

limit

Gas in the path

Make sure that the path is
clean and the weather

conditions are good

NQRat1 and NQRat2
above the permitted

limit

Poor alignment

Perform alignment

R/N, S1/N, S2/N
below 50

Poor alignment

Perform alignment

Dirt on the
window

Clean the window

Poor light source Replace the light source
Detector fault

Replace/repair Detector

Temperature higher
than 25° C beyond
the room

temperature

Electronic
problem

Replace/repair Detector

Ratio1 and Ratio2 out
of the limit

Poor alignment

Perform alignment

Dirt on the
window

Clean the window

Detector fault

Replace/repair Detector

Voltage less than 16V
DC. The Detector at

“V” fault

Low input
voltage

Check the power supply and
installation