Bias (manual reset), On/off differential, Setpoint high limit – West Control Solutions N8100 User Manual

Page 18: Setpoint low limit, Recorder output scale maximum, Recorder output scale minimum

Advertising
background image

2.2.10

Bias (Manual Reset)

This bias to the output power is expressed as a percentage of output power. This

parameter is not applicable if Proportional Band 1 = 0.

2.2.11

ON/OFF Differential

This is a switching differential used when one or both outputs have been set to

ON/OFF control (i.e. Proportional Band 1 or Proportional Band 2 or both = 0).

2.2.12

Setpoint High Limit

This is the maximum limit for setpoint adjustment. It should be set to a value which

prevents the setpoint being given a value which will cause damage to the

process being controlled.

2.2.13

Setpoint Low Limit

This is the minimum limit for setpoint adjustment. It should be set to a value which

prevents the setpoint being given a value which will cause damage to the

process being controlled.

2.2.14

Recorder Output Scale Maximum

This parameter defines the value of process variable or setpoint (whichever is

applicable) at which the Recorder Output reaches its maximum value; for

example, for a 0 - 5V Recorder Output, this value corresponds to 5V. The decimal

point position for the Recorder Output is always the same as that for the process

variable input range. This parameter is not applicable if the Recorder Output

option is not fitted.

NOTE: If this parameter is set to a value less than that for the Recorder

Output Scale Minimum (see Subsection 2.2.15), the relationship between

the process variable/setpoint value and the Recorder Output is reversed.

2.2.15

Recorder Output Scale Minimum

This parameter defines the value of the process variable or setpoint (whichever is

applicable) at which the Recorder Output reaches its minimum value; for

example, for a 0 - 5V Recorder Output, this value corresponds to 0V. The decimal

point position for the Recorder Output is always the same as that for the process

variable input range. This parameter is not applicable if the Recorder Output

option is not fitted.

NOTE: If this parameter is set to a value greater than that for the Recorder

Output Scale Maximum (see Subsection 2.2.14), the relationship between

the process variable value and the Recorder Output is reversed.

2-7

O054-2

59125