2.2.30

Scale Range Maximum

This parameter, applicable only if a linear input is fitted, defines the scaled input

value when the process variable input hardware is at its maximum value. This

parameter can be set to a value less than (but not equal to) Scale Range

Minimum, in which case the sense of the input is reversed. Decimal point position

is defined by the Scale Range Decimal Point parameter (see Subsection 2.2.29).

2.2.31

Scale Range Minimum

This parameter, applicable only if a linear input is fitted, defines the scaled input

value when the process variable input hardware is at its minimum value. This

parameter can be set to a value greater than (but not equal to) Scale Range

Maximum, in which case the sense of the input is reversed. Decimal point position

is defined by the Scale Range Decimal Point parameter (see Subsection 2.2.29).

2.2.32

Auto Pre-Tune Enable/Disable

This parameter determines whether or not the Controller’s Pre-Tune facility is

activated automatically on power-up or not.

2.2.33

Manual Control Enable/Disable

This parameter determines whether operator selection of manual control is

enabled or disabled.

2.2.34

Setpoint Ramp Enable/Disable

This parameter enables/disables use of the setpoint ramping feature at user level.

2.2.35

Setpoint Strategy

This parameter enables the user to select the required Operator Mode setpoint

display strategy - see Subsections 1.2.1 (Single Setpoint operation) and 1.2.2 (Dual

Setpoint operation).

2.2.36

Communications Enable/Disable

This parameter enables/disables Write operations (i.e. the changing of parameter

values/settings) via the RS485 communications link, if the Communications Option

PCB is fitted. Parameters can be interrogated via the link, regardless of the setting

of this parameter.

2.2.37

Lock Value

This parameter defines the four-digit code required to enter Set Up Mode.