Dc linear, Dual setpoint selection input (option), Available, refer to appendix a – West Control Solutions N8100 User Manual

Page 68: A.2 dual setpoint selection input (option)

Advertising
background image

Input

Type

Location of Break

Alarm Operation

1

4

-DIN or

1

8

-DIN Controller

1

16

-DIN Controller

RTD

Sensor or Terminal 1

Sensor or Terminal 6

As if Process Variable is over-range

RTD

Terminal 3 or 2

Terminal 4 or 5

As if Process Variable is under-range

DC (mV) -

-

As if Process Variable is over-range

DC Linear: Ranges Selectable from Front Panel (with displayed codes):

(Changes may also be required to the CPU PCB link jumpers - see Subsection 2.5)

Scale Range Maximum:

–1999 to 9999. Decimal point as required.

Scale Range Minimum:

–1999 to 9999. Decimal point as for Scale

Range Maximum.

Minimum Span:

1 display LSD.

Sensor Break Protection:

Applicable to 4 - 20mA, 1 - 5V and 2 - 10V

ranges only. Break detected within two

seconds. Control outputs set to OFF (0%

power); Alarms operate as if the process

variable has gone under-range.

A.2

DUAL SETPOINT SELECTION INPUT (OPTION)

Type:

Voltage-free or TTL-compatible

Voltage-Free Operation:

Connection to contacts of external switch

or relay; contacts open = Setpoint 1

selected (minimum contact resistance =

5000

), contacts closed = Setpoint 2

selected (maximum contact resistance =

50

).

TTL levels:

To select Setpoint 1: –0.6V to 0.8V

To select Setpoint 2: 2.0V to 24V

A-3

S054-A

59125

Input Range

Displayed Code

Input Range

Displayed Code

0 - 20mA

3413

0 - 5V

4445

4 - 20mA *

3414

1 - 5V

4434

0 - 50mV

4443

0 - 10V *

4446

10 - 50mV

4499

2 - 10V

4450