3.3.2

Output Parameters

3-6

O054-3

59125

Parameter

Identifier

Description

Power Output

value

W

If Manual Control is not selected, may be read

only (Type 2 message). If Manual Control is

selected, may be read (Type 2 message) or

modified (Type 3/Type 4 message sequence).

Output 1 Power

Limit

B

May be read (Type 2 message) or modified (Type

3/Type 4 message sequence). Defines power limit

for Output 1.

Output 1 Cycle

Time

N

May be read (Type 2 message) or modified (Type

3/Type 4 message sequence). NOTE: Value must

be a power of 2 in the range 0.5 - 512 (i.e. 0.5, 1,

2, 4, 8 etc.). For a Relay Output, cycle time should

be as large as possible (whilst remaining

compatible with the process control requirements)

in order to maximise relay life. For an SSR Output,

the cycle time may have a lower value (and thus

satisfy the requirements of a fast-changing

process variable e.g. flow or pressure).

Output 2 Cycle

Time

O

May be read (Type 2 message) or modified (Type

3/Type 4 message sequence). NOTE: Value must

be a power of 2 in the range 0.5 - 512 (i.e. 0.5, 1,

2, 4, 8 etc.). For a Relay Output, cycle time should

be as large as possible (whilst remaining

compatible with the process control requirements)

in order to maximise relay life. For an SSR Output,

the cycle time may have a lower value (and thus

satisfy the requirements of a fast-changing

process variable e.g. flow or pressure).

Recorder Output

Scale Max.

[

May be read/modified by a Type 2 message or a

Type 3/Type 4 message sequence. Corresponds to

Input Scale Max. with decimal point position as for

input. If less than Recorder Output Scale Min.

sense of recorder output is reversed.

Recorder Output

Scale Min.

\

May be read/modified by a Type 2 message or a

Type 3/Type 4 message sequence. Corresponds to

Input Scale Min. with decimal point position as for

input. If greater than Recorder Output Scale Max.

sense of recorder output is reversed.