Resistance temperature detector (rtd) and dc mv – West Control Solutions N8100 User Manual

Page 67

Advertising
background image

Calibration:

Complies with BS4937, NBS125 and IEC584.

Sensor Break Protection:

Break detected within two seconds. Control

outputs set to OFF (0% power); Alarms

operate as if the process variable has

gone over-range.

Resistance Temperature Detector (RTD) and DC mV: Ranges selectable

from front panel (with displayed codes):

Type and Connection:

Three-wire Pt100

Calibration:

Complies with BS1904 and DIN43760.

Lead Compensation:

Automatic scheme.

RTD Sensor Current:

150

µ

A (approximately)

Sensor Break Protection:

Break detected within two seconds. Control

outputs set to OFF (0% power). Alarm

operation is as follows:

S054-A

A-2

59125

Type

Input Range

Dislayed Code

Type

Input Range

Displayed Code

L

0.0 - 205.7

°

C

1815

L

32 - 1403

°

F

1820

L

32.0 - 402.2

°

F

1816

B

211 - 3315

°

F

1934

L

0 - 450

°

C

1817

B

100 - 1824

°

C

1938

L

32 - 841

°

F

1818

N

0 - 1399

°

C

5371

L

0 - 762

°

C

1819

N

32 - 2550

°

F

5324

Input Range

Displayed Code

Input Range

Displayed Code

0 - 800

°

C *

7220

0.0 - 100.9

°

C

2295

32 - 1471

°

F

7221

32.0 - 213.6

°

F

2296

32 - 571

°

F

2229

-200 - 206

°

C

2297

-100.9 - 100.0

°

C

2230

-328 - 402

°

F

2298

-149.7 - 211.9

°

F

2231

-100.9 - 537.3

°

C

7222

0 - 300

°

C

2251

-149.7 - 999.1

°

F

7223

Advertising
This manual is related to the following products: