Selection of output 1 type, 1/16-din controllers, 1/4-din and 1/8-din controllers – West Control Solutions N8100 User Manual

Page 53: Output 2 type/output 3 type

Advertising
background image

2.6

SELECTION OF OUTPUT 1 TYPE

2.6.1

1

16

-DIN Controllers

The required type of Output 1 is

selected by Link Jumpers LJ4, LJ5,

LJ6 and LJ7 on the Relay/SSR Output

1 CPU PCB (see Figure 2-4) or, on the

DC Output 1 CPU PCB, Link Jumpers

LJ8 and LJ9 (see Figure 2-5). Output

type selection is as shown on the

right.

2.6.2

1

4

-DIN and

1

8

-DIN

Controllers

The required type of Output 1 is

selected by Link Jumpers LJ4, LJ5,

LJ6, LJ7, LJ8 and LJ9 on the PSU PCB

(see Figure 2-7). Output type

selection is as shown on the right.

2.7

OUTPUT 2 TYPE/OUTPUT 3 TYPE

The type of output for Output 2 and Output 3 is determined by the Option PCB

fitted in the appropriate position (see Figure 2-1). There are four types of option

PCB which may be used for Output 2 and Output 3:

1. Relay Output Option PCB (no link jumpers)

2. Solid State Output Option PCB (no link jumpers)

3. SSR Output Option PCB (no link jumpers)

4. DC Output Option PCB (link jumpers as shown in Figure 2-8)

In the case of the DC Output Option

PCB being fitted, DC output range is

selected using link jumpers LJ8 and

LJ9, as shown on the right.

S054-2

2-5

59125

Output 1 Type

Link Jumpers Fitted

Relay or Solid State

LJ5 & LJ6

SSR Drive

LJ4 & LJ7

DC (0 - 10V)

LJ8

DC (0 - 20mA)

LJ9

DC (0 - 5V)

LJ8

DC (4 - 20mA)

LJ9

Output 1 Type

Link Jumpers Fitted

Relay or Solid State

LJ5 & LJ6

SSR Drive

LJ4 & LJ7

DC (0 - 10V)

LJ8

DC (0 - 20mA)

LJ9

DC (0 - 5V)

LJ8

DC (4 - 20mA)

LJ9

DC Output Range

Link Jumpers Fitted

DC (0 - 10V)

LJ8

DC (0 - 20mA)

LJ9

DC (0 - 5V)

LJ8

DC (4 - 20mA)

LJ9

Advertising
This manual is related to the following products: