background image

Isolation:

Isolated from all other inputs and outputs.

Range Selection Method:

Link jumper or DIP switch and front panel

code.

A.5

OUTPUT 3

General

Types Available:

Relay, SSR drive, solid state and DC linear

(Recorder Output only)

Relay

Contact Type:

Single pole double throw (SPDT).

Rating:

2A resistive at 120/240V AC.

Lifetime:

>500,000 operations at rated

voltage/current.

Isolation:

Inherent.

SSR Drive/TTL

Drive Capability:

SSR >4.2V DC into 1k

min. (

1

16

-DIN)

SSR > 4.3V into 250

min. (

1

4

-DIN &

1

8

-DIN)

Isolation:

Not isolated from input or other SSR drive

outputs.

Solid State

Operating Voltage Range:

20 - 280Vrms (47 - 63Hz)

Current Rating:

0.01 - 1A (full cycle rms on-state @ 25

°

C);

derates linearly above 40

°

C to 0.5A @

80

°

C.

Max. Non-repetitive Surge

Current (16.6ms):

25A peak

Min. OFF-State

dv

dt

@ Rated

Voltage:

500V/

µ

s

Max. OFF-State leakage @

Rated Voltage:

1mA rms