The controller attempts to calculate the optimum control parameters from the

process response. If this is done successfully, the optimized parameters are taken

over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.

After completing the 1st step as described, a correcting variable of -100% (100%

cooling energy) is output from the set-point. After successfull determination of

the “cooling parameters”, line-out to the set-point is using the optimized

parameters.
Pulse attempt after start-up

Condition: - tunE = 1 and sufficient set-point reserve provided.
The controller outputs 0% correcting variable or Y.Lo and waits, until the process

is at rest (see start conditions page 16)

Subsequently, a short pulse of 100% is output (Y=100%) and reset.

The controller attempts to determine the optimum control parameters from the

process response. If this is completed successfully, these optimized parameters

are taken over and used for line-out to the set-point.
With a 3-point controller, this is followed by “cooling”.

After completing the 1st step as described and line-out to the set-point, correcting

variable "heating" remains unchanged and a cooling pulse (100% cooling energy)

is output additionally. After successful determination of the “cooling

parameters”, the optimized parameters are used for line-out to the set-point.

Optimization at the set-point

Conditions:

w A sufficient set-point reserve is not provided at self-tuning start (see page 17).

w tunE is 0 or 1

w With Strt = 1 configured and detection of a process value oscillation by

more than ± 0,5% of (rnG.H - rnG.L) by the controller, the control

parameters are preset for process stabilization and the controller realizes an

optimization at the set-point (see figure “Optimization at the set-point”).

w when the step attempt after power-on has failed

w with active gradient function ( PArA/ SETP/ r.SP≠ OFF), the set-point

gradient is started from the process value and there isn't a sufficient set-point

reserve.

Operation

Self-tuning

18

8800 process controller