7 second pid parameter set 26, Manual tuning 26, 8 alarm handling – West Control Solutions N8800 User Manual

Page 26: Ü operaing principle absolute alarm l.1 = off, Operating principle relative alarm l.1 = off, H.1 = off

Advertising
background image

3.8 Alarm handling

Max. three alarms can be configured and assigned to the individual outputs.

Generally, outputs OuT.1... OuT.6 can be used each for alarm signalling. If

more than one signal is linked to one output the signals are OR linked. Each of

the 3 limit values Lim.1 … Lim.3 has 2 trigger points H.x (Max) and L.x (Min),

which can be switched off individually (parameter = “OFF”). Switching

difference HYS.x and delay dEl.x of each limit value is adjustable.

1: normally closed ( ConF/ Out.x / O.Act=1 )
2: normally open ( ConF/ Out.x / O.Act= 0 )

Operation

Alarm handling

26

8800 process controller

H.1

LED

HYS.1

InL.1

InH.1

2

1

Ü Operaing principle absolute alarm

L.1 = OFF

LED

HYS.1

H.1

InL.1

InH.1

SP

2

1

* Operating principle relative alarm

L.1 = OFF

L.1

LED

HYS.1

InL.1

InH.1

2

1

H.1 = OFF

L.1

LED

HYS.1

InL.1

InH.1

SP

2

1

H.1 = OFF

L.1

LED

LED

HYS.1

HYS.1

H.1

InL.1

InH.1

2

2

1

L.1

LED

LED

HYS.1

HYS.1

H.1

InL.1

InH.1

SP

2

2

1

Advertising