West Control Solutions N8800 User Manual

Page 21

Advertising
background image

3.5.4 Self-tuning start

Start condition:

w For process evaluation, a stable condition is required. Therefore, the

controller waits until the process has reached a stable condition after

self-tuning start.

The rest condition is considered being reached, when the process value

oscillation is smaller than ± 0,5% of (rnG.H - rnG.L).

w For self-tuning start after start-up, a 10% difference from (SP.LO ... SP.Hi)

is required.

g

Self-tuning start can be blocked via 8800/8840 configurator

®

(engineering tool)

( P.Loc).

Strt = 0

Only manual start by pressing keys Ù and È

simultaneously or via interface is possible.

Strt = 1

Manual start by press keys Ù and È simultaneously

via interface and automatic start after power-on and detection

of process oscillations.

3.5.5 Self-tuning cancellation

By the operator:

Self-tuning can always be cancelled by the operator. For this, press Ù and È

key simultaneously.With controller switch-over to manual mode after self-tuning

start, self-tuning is cancelled. When self-tuning is cancelled, the controller will

continue operating using the old parameter values.
By the controller:

If the Err LED starts blinking whilst self-tuning is running, successful self-tuning

is prevented due to the control conditions. In this case, self-tuning was cancelled

by the controller. The controller continues operating with the old parameters in

automatic mode. In manual mode it continues with the old controller output

value.

3.5.6 Acknowledgement procedures in case of unsuccessful self-tuning

Operation

8800 process controller

21

Self-tuning

Ada LED status

Signification

blinks

Waiting, until process

calms down

lit

Self-tuning is running

off

Self-tuning not activ

or ended