Configuration level

8800 process controller

35

Configuration parameters

Lim

Name

Value range Description

Default

Fnc.1

Function of limit 1

1

0

switched off

1

measured value monitoring

2

Measured value monitoring + alarm status storage. A stored

limit value can be reset via error list,

è

-key, Ò-key or a

digital input ( -> LOGI/ Err.r)

3

signal change (change/minute)

4

signal change and storage (change/minute)

Src.1

Source of imit 1

1

0

process value

1

control deviation xw (process value - set-point)

2

control deviation xw (with suppression after start-up and

set-point change)
After switch-on or set-point changing, the alarm output is

suppressed, until the process value is within the limits for the first

time. At the latest after elapse of time 10 ti1the alarm is

activated (ti1 = integral time 1; parameter r Cntr)

If ti1 is switched off (ti1 = 0), this is interpreted as Î , i.e.

the alarm is not activated, before the process value was within the

limits once.

3

measured value INP1

4

measured value INP2

5

measured value INP3

6

effective setpoint Weff

7

correcting variable y (controller output)

8

control variable deviation xw (actual value - internal setpoint)

= deviation alarm to internal setpoint

9

difference x1 - x2 (utilizable e.g. in combination with process

value function “mean value” for recognizing aged

thermocouples

Fnc.2

Function of limit 2

0

0

switched off

1

measured value monitoring

2

Measured value monitoring + alarm status storage. A stored

limit value can be reset via error list,

è

-key, Ò-key or a

digital input ( -> LOGI/ Err.r)

3

signal change (change/minute)

4

signal change and storage (change/minute)