Measurement – West Control Solutions N8800 User Manual

Page 71

Advertising
background image

7.2.2 Configuration:

Oxygen measurement

Oxygen measurement with heated lambda probe

Controller r Process value processing r 7: O

2

functions with constant probe

temperature

Cntr r C.tYP

7

O2-const

Oxygen measurement with non-heated lambda probe

Controller r Process value processing r O

2

functions with measured probe

temperature

Cntr r C.tYP

8

O2+temp

Input 1 r Function INP1 r 7: process value X1

InP.1 r 1.Fnc

7

X1-Input

In input 1, the sensor type is set for one of the high-impedance voltage inputs:

Input 1 r Sensor type r 42: special (-25...1150 mV) or

41: special (-2,5...115 mV)

InP.1 r S.tyP

41

115 mV

InP.1 r S.tyP

42

1150 mV

Input 1 r meas. value correction r 0: no correction

InP.1 r S.Lin

0

no

Temperature measurement (required with non-heated lambda probe)

Any temperature measurement with one of analog inputs INP2 or INP3 can be

used. Select input X2 during function selection (second set-point).

g

With O

2

measurement, evaluation in ppm or % must be specified for all

parameters related to the process value.

This is done centrally during configuration.
Other r Parameter unit for O

2

r 0: parameter for O

2

function in ppm

1: parameter for O

2

function in %

othrr O2

0

unit : ppm

othrr O2

1

unit : %

g

Whether the temperature of the non-heated λ probe is specified in °C or °F can

be selected during configuration.

Other r Unit r 1: in Celsius

2: in Fahrenheit

othrr Unit

1

°C

othrr Unit

2

°F

Special functions

8800 process controller

71

O

2

measurement