4 switching behaviuor 50, 1 standard ( cycl= 0 ) 50, 2 switching attitude linear ( cycl= 1 ) 50 – West Control Solutions N8800 User Manual

Page 50: Set-point processing 50

Advertising
background image

Parameters to be adjusted: E.H2O: minimum temperature for water cooling

( PArA / Cntr)

t.on:

pulse duration water cooling

t.off: minimum pause water cooling

4.4.3 Switching attitude non-linear ( CyCl= 2 )

With this method, the cooling power

is normally much higher than the

heating power, i.e. the effect on the

behaviour during transition from

heating to cooling may be negative.

The cooling curve ensures that the

control intervention with 0 to -70%

correcting variable is very weak.

Moreover, the correcting variable increases very quickly to max. possible

cooling. Parameter F.H2O can be used for changing the characteristic curve. The

standard method (see section 4.4.1) is also used for heating. Cooling is also

enabled dependent of process temperature .

Parameters to be adjusted: F.H2O: adaptation of (non-linear) characteristic

( PArA / Cntr)

Water cooling

t.on:

Pulse duration water cooling

t.off: min. pause water cooling

E.H2O: min. temperature for water cooling

Configuration level

Switching behaviuor

50

8800 process controller

-95% -67% -80% -100%

-92%

-90%

-87%

-82%

t.off

t.on

0

10

20

30

40

50

60

70

-100

-95

-90

-85

-80

-75

-70

-65

-60

-55

-50

-45

-40

-35

-30

-25

-20

-15

-10

-5

Controller output [%]

Water cooling non-linear,

=1

F.H2O

Water cooling non-linear,

=2

F.H2O

Water cooling non-linear,

=0,5

F.H2O

Water cooling linear

Parameter:
t.on = 0.4 sec
t.off = 0.2 sec

Effective

controller

output

Advertising