Easicool™eze precision air conditioning, Technical data upflow units wx type, Te ch nic al w x - t yp e v – Airedale EasiCool 6kW 64kW User Manual

Page 119: Performance data

Advertising
background image

EasiCool™EZE

Precision Air Conditioning

Technical Data Upflow Units WX Type

Performance Data

Cooling Capacity (1)

Condenser Entering/Leaving Temperature - Based on 5°C ΔT

Air On

25°C/30°C

30°C/35°C

35°C/40°C

40°C/45°C

(DB°C/%RH) TC (kW) SC (kW)

THR

(kW)

TC (kW) SC (kW)

THR

(kW)

TC (kW) SC (kW)

THR

(kW)

TC (kW) SC (kW)

THR

(kW)

V28WX2-EZE

22/50

31.8

29.0

34.9

30.7

28.4

35.7

29.5

27.8

36.4

28.2

27.1

37.2

24/45

32.7

31.5

35.8

31.5

30.8

36.6

30.3

30.2

37.3

29.0

29.0

38.1

26/40

32.5

32.5

35.8

31.3

31.3

36.7

30.2

30.2

37.5

29.2

29.2

38.4

V31WX-EZE

22/50

33.7

32.1

36.9

32.5

31.4

37.7

31.2

30.7

38.5

29.8

29.8

39.3

24/45

34.7

34.7

38.0

33.5

33.5

38.8

32.2

32.2

39.5

30.8

30.8

40.3

26/40

35.4

35.4

38.7

34.2

34.2

39.5

32.9

32.9

40.3

31.5

31.5

41.1

V31WX2-EZE

22/50

36.2

33.5

39.7

35.0

32.8

40.7

33.7

32.1

41.7

32.2

31.2

42.8

24/45

37.3

36.2

40.8

36.1

35.5

41.8

34.7

34.7

42.8

33.2

33.2

43.8

26/40

38.0

38.0

41.5

36.7

36.7

42.5

35.4

35.4

43.5

33.9

33.9

44.6

V35WX-EZE

22/50

40.0

38.0

43.7

38.6

37.2

44.7

37.0

36.3

45.7

35.3

35.3

46.7

24/45

41.2

41.2

45.0

39.7

39.7

46.0

38.1

38.1

46.9

36.4

36.4

48.0

26/40

42.1

42.1

45.9

40.6

40.6

46.9

39.0

39.0

47.8

37.2

37.2

48.8

V35WX2-EZE

22/50

39.4

37.6

43.0

37.9

36.8

43.7

36.2

35.9

44.4

34.4

34.4

45.2

24/45

40.6

40.6

44.3

39.0

39.0

44.9

37.3

37.3

45.6

35.5

35.5

46.4

26/40

41.5

41.5

45.2

39.9

39.9

45.8

38.1

38.1

46.5

36.3

36.3

47.2

V40WX-EZE

22/50

43.9

42.2

48.0

42.3

41.3

49.2

40.7

40.5

50.5

39.1

39.1

51.8

24/45

45.9

45.9

50.0

44.5

44.5

51.3

42.9

42.9

52.6

41.2

41.2

53.9

26/40

47.0

47.0

51.2

45.6

45.6

52.4

44.0

44.0

53.7

42.3

42.3

55.1

V40WX2-EZE

22/50

42.3

41.4

46.3

40.5

40.4

47.4

38.9

38.9

48.6

37.2

37.2

49.8

24/45

44.4

44.4

48.4

42.8

42.8

49.5

41.1

41.1

50.6

39.2

39.2

51.7

26/40

45.5

45.5

49.6

43.9

43.9

50.7

42.2

42.2

51.8

40.4

40.4

53.0

V45WX2-EZE

22/50

46.6

43.6

50.2

44.8

42.7

51.4

42.8

41.6

52.7

40.8

40.6

53.9

24/45

47.9

47.3

51.6

46.1

46.1

52.8

44.1

44.1

54.0

42.0

42.0

55.2

26/40

49.0

49.0

52.8

47.2

47.2

53.9

45.2

45.2

55.2

43.1

43.1

56.3

V50WX2-EZE

22/50

57.6

51.8

62.0

55.7

50.7

63.7

53.6

49.6

65.5

51.4

48.4

67.3

24/45

57.7

55.8

62.2

55.6

54.6

64.0

53.5

53.4

65.8

51.5

51.5

67.6

26/40

60.4

60.3

65.0

58.5

58.5

66.7

56.3

56.3

68.4

54.1

54.1

70.2

V55WX2-EZE

22/50

63.5

55.1

68.4

61.3

53.9

70.2

58.8

52.6

72.2

56.4

51.3

74.1

24/45

65.2

59.4

70.2

63.0

58.3

72.0

60.5

57.0

73.9

58.0

55.8

75.8

26/40

66.7

64.0

71.8

64.4

62.8

73.6

61.9

61.5

75.4

59.3

59.3

77.2

V60WX2-EZE

22/50

67.5

59.1

72.7

65.1

57.8

74.7

62.5

56.5

76.7

59.8

55.1

78.7

24/45

69.2

63.9

74.6

66.8

62.7

76.5

64.2

61.3

78.5

61.4

59.9

80.4

26/40

72.6

70.1

78.2

70.5

69.0

80.5

68.2

67.8

82.9

65.9

65.9

85.2

TC = Total Cooling
SC = Sensible Cooling
THR = Total Heat Rejection

(1) All data quoted is gross
(2) Interpolate for water temperatures between those quoted, do not extrapolate
(3) Water flow rate (l/s) = THR/(4.19*ΔT) at 100% Water; for glycol use refer to Ethylene Glycol

Correction Factors section

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55%

Condenser Minimum Entering Temperature °C

+25°C

Condenser Maximum Leaving Water Temperature °C +45°C

119

EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013