V31X - V31X2

Technical Data Upflow Units X Type

Electrical Data

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

V31X-EZE-0

V31X2-EZE-0

Standard Condenser Match

C45

C45

Unit Data Full Function

(1)

Nominal Run Amps

A

63.6

64.7

Maximum Start Amps

A

180.3

129.5

Recommended Mains Fuse Size

A

80

80

Unit Data Cooling Only

(2)

Nominal Run Amps

A

31.2

32.3

Maximum Start Amps

A

147.9

97.1

Recommended Mains Fuse Size

A

40

40

Max Mains Incoming Cable Size

mm²

35

35

Mains Supply

V

400V / 3PH + N / 50HZ

Control Circuit

VAC

24

24

Evaporator Fan - Per Fan
Maximum Electrical Input Power

(3)

kW

1 x 4

1 x 4

Full Load Amps

A

8.12

8.12

Locked Rotor Amps

A

60.9

60.9

Compressor - Per Compressor
Quantity x Motor Size

kW

1 x 9.73

2 x 6.5

Nominal Run Amps

A

17.3

9.2

Locked Rotor Amps

A

134

74

Type of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size

kW

2 x 0.6

2 x 0.6

Full Load Amps

A

2.62

2.62

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

3

3

Number of Elements

9

9

Rating

kW

22.5

22.5

Curent per Phase

A

32.48

32.48

Humidifier
Capacity

kg/hr

8

8

Rating

kW

6

6

Full Load Amps

A

8.66

8.66