Easicool™eze precision air conditioning, Electrical data – Airedale EasiCool 6kW 64kW User Manual

Page 71

Advertising
background image

EasiCool™EZE

Precision Air Conditioning

DF35X - DF45X

71

EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013

Te

ch

nic

al

X-T

yp

e

DF

Technical Data Downflow Units X Type

Electrical Data

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

DF35X-EZE-0

DF40X-EZE-0

DF45X-EZE-0

Standard Condenser Match

CS50

CS50

CS50

Unit Data Full Function

(1)

Nominal Run Amps

A

65.4

72.0

75.1

Maximum Start Amps

A

191.3

194.1

224.1

Recommended Mains Fuse Size

A

80

80

100

Unit Data Cooling Only

(2)

Nominal Run Amps

A

33.0

39.5

42.6

Maximum Start Amps

A

158.9

161.6

191.6

Recommended Mains Fuse Size

A

40

50

50

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

Mains Supply

Control Circuit

VAC

24

24

24

Evaporator Fan - Per Fan
Maximum Electrical Input Power

(3)

kW

1 x 4

1 x 5.5

1 x 5.5

Full Load Amps

A

8.12

10.9

10.9

Locked Rotor Amps

A

60.9

69.8

69.8

Compressor - Per Compressor
Quantity x Motor Size

kW

1 x 11

1 x 11.9

1 x 13.2

Nominal Run Amps

A

19.1

22.9

26

Locked Rotor Amps

A

145

145

175

Type of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size

kW

2 x 0.6

2 x 0.6

2 x 0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

3

3

3

Number of Elements

8

8

8

Rating

kW

20

20

20

Curent per Phase

A

32.48

32.48

32.48

Humidifier
Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.24

16.24

16.24

Advertising