Easicool™eze precision air conditioning, Dimensional & installation data, Ins ta lla tio n – Airedale EasiCool 6kW 64kW User Manual

Page 41: Weights upflow

Advertising
background image

EasiCool™EZE

Precision Air Conditioning

(1)

Weights quoted for units fitted with the standard forward curved EC fan motor

include the cooling fan weight within the unit cabinet (AHU).

(2)

Machine weight includes a refrigerant charge / Operating weight includes calculated water volume..

Dimensional & Installation Data

Weights

Upflow

Standard Evaporator

Fan - Fwd EC Motor

Optional Evaporator

Fan - Bkwd EC Motor

Machine

Operating

Machine

Operating

V6X

kg

174

165

V8X

kg

173

166

V10X

kg

177

174

V13X

kg

211

213

V15X

kg

235

220

V17X

kg

236

221

V20X2

kg

289

285

V22X2

kg

289

285

V26X2

kg

289

285

V28X

kg

422

415

V28X2

kg

431

424

V31X

kg

414

407

V31X2

kg

447

440

V35X

kg

476

465

V35X2

kg

518

507

V40X

kg

504

475

V40X2

kg

532

503

V45X2

kg

538

509

V50X2

kg

639

609

V55X2

kg

656

626

V60X2

kg

660

630

Standard Evaporator

Fan - Fwd EC Motor

Optional Evaporator

Fan - Bkwd EC Motor

Machine

Operating

Machine

Operating

V6WX

kg

189

191

180

182

V8WX

kg

193

194

186

187

V10WX

kg

196

197

193

194

V13WX

kg

234

235

236

237

V15WX

kg

265

267

250

252

V17WX

kg

268

270

253

255

V20WX2 kg

326

328

322

324

V22WX2 kg

326

328

322

324

V26WX2 kg

325

328

321

324

V28WX

kg

478

484

471

477

V28WX2 kg

487

493

480

486

V31WX

kg

470

476

463

469

V31WX2 kg

502

508

495

501

V35WX

kg

536

542

525

531

V35WX2 kg

578

584

567

573

V40WX

kg

569

575

540

546

V40WX2 kg

596

602

567

573

V45WX2 kg

627

637

598

608

V50WX2 kg

729

739

699

709

V55WX2 kg

749

759

719

729

V60WX2 kg

753

763

723

733

41

EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013

Ins

ta

lla

tio

n

Advertising