Easicool™eze precision air conditioning, Performance data standard condenser, Operating limits – Airedale EasiCool 6kW 64kW User Manual

Page 56

Advertising
background image

EasiCool™EZE

Precision Air Conditioning

Cooling Capacity (1)

Ambient

Air On

25°C

30°C

35°C

40°C

(DB°C/%RH)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

TC (kW)

SC (kW)

DF6X-EZE C11

22/50

6.6

5.9

6.1

5.7

6.1

5.7

5.9

5.6

24/45

6.8

6.5

6.3

6.3

6.3

6.3

6

6

26/40

7

7

6.4

6.4

6.4

6.4

6.2

6.2

DF8X-EZE C15

22/50

9.3

8.1

8.6

7.7

8.6

7.7

8.3

7.6

24/45

9.5

8.7

8.9

8.4

8.9

8.4

8.5

8.2

26/40

9.8

9.4

9.2

9.1

9.1

9.1

8.8

8.8

DF10X-EZE C15

22/50

10.5

9.6

9.9

9.2

9.8

9.2

9.4

8.9

24/45

10.8

10.4

10.3

10

10.1

9.9

9.7

9.6

26/40

11.2

11.1

10.7

10.7

10.5

10.5

10.1

10.1

DF13X-EZE C20

22/50

13.9

11.6

13

11.2

12.8

11.1

12.2

10.9

24/45

14.3

12.6

13.4

12.2

13.2

12.1

12.6

11.8

26/40

14.6

13.9

13.7

13.6

13.4

13.4

12.8

12.8

DF15X-EZE C25

22/50

16.7

13.9

15.7

13.4

15.3

13.3

14.5

12.9

24/45

17

15

16.2

14.7

15.7

14.5

15

14.2

26/40

17.4

16.3

16.6

16

16

15.7

15.4

15.4

DF17X-EZE C35

22/50

20

17.4

18.6

16.7

18.5

16.6

17.6

16.2

24/45

20.5

18.8

19.2

18.2

19

18.1

18.1

17.6

26/40

20.9

20.3

19.6

19.6

19.4

19.4

18.5

18.5

DF22X2-EZE C45

22/50

25.5

20.5

23.4

19.6

23.4

19.6

22.4

19.2

24/45

26.6

22.4

24.7

21.5

24.7

21.5

23.6

21

26/40

27.4

24.2

25.5

23.3

25.4

23.3

24.2

22.8

DF25X2-EZE C45

22/50

26.6

22.4

24.7

21.5

24.7

21.5

23.5

20.9

24/45

27.4

24.4

25.5

23.6

25.4

23.5

24.3

23

26/40

28.1

26.6

26.2

25.7

26.1

25.6

24.9

24.9

DF26X-EZE C45

22/50

28

25

26

23.9

25.8

23.8

24.5

23.1

24/45

28.7

27

26.8

26

26.5

25.8

25.2

25.1

26/40

29.3

29.1

27.4

27.4

27.1

27.1

25.7

25.7

56

EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013

Te

ch

ni

ca

l

X-

Ty

pe

DF

Technical Data Downflow Units X Type

Performance Data

Standard Condenser

TC = Total Cooling
SC = Sensible Cooling

(1) All data quoted is gross

Operating Limits

Indoor Air Temperature

+18°C to +28°C

Indoor RH%

+40% to +55% (based upon 24°C Dry Bulb)

Outdoor Temperature

-20°C to +41°C

Advertising