Easicool™eze precision air conditioning, Electrical data – Airedale EasiCool 6kW 64kW User Manual

Page 67

Advertising
background image

EasiCool™EZE

Precision Air Conditioning

DF22X2 - DF25X2

67

EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013

Te

ch

nic

al

X-T

yp

e

DF

Technical Data Downflow Units X Type

Electrical Data

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.

DF22X2-EZE-0

DF25X2-EZE-0

Standard Condenser Match

C45

C45

Unit Data Full Function

(1)

Nominal Run Amps

A

39.9

39.9

Maximum Start Amps

A

83.4

83.4

Recommended Mains Fuse Size

A

50

50

Unit Data Cooling Only

(2)

Nominal Run Amps

A

18.2

18.2

Maximum Start Amps

A

61.7

61.7

Recommended Mains Fuse Size

A

25

25

Max Mains Incoming Cable Size

mm²

35

35

Mains Supply

V

400V / 3PH + N / 50HZ

Control Circuit

VAC

24

24

Evaporator Fan - Per Fan
Maximum Electrical Input Power

(3)

kW

2 x 1.15

2 x 1.15

Full Load Amps

A

4.8

4.8

Locked Rotor Amps

A

4.8

4.8

Compressor - Per Compressor
Quantity x Motor Size

kW

2 x 4.7

2 x 4.7

Nominal Run Amps

A

6.5

6.5

Locked Rotor Amps

A

50

50

Type of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size

kW

2 x 0.6

2 x 0.6

Full Load Amps

A

2.62

2.62

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

2

2

Number of Elements

6

6

Rating

kW

15

15

Curent per Phase

A

21.65

21.65

Humidifier
Capacity

kg/hr

3

3

Rating

kW

2.25

2.25

Full Load Amps

A

3.25

3.25

Advertising