Easicool™eze precision air conditioning, Electrical data – Airedale EasiCool 6kW 64kW User Manual

Page 73

Advertising
background image

EasiCool™EZE

Precision Air Conditioning

DF50X2 - DF60X2

DF50X2-EZE-0

DF55X2-EZE-0

DF60X2-EZE-0

Standard Condenser Match

CS65

CS80

CS80

Unit Data Full Function

(1)

Nominal Run Amps

A

89.7

89.9

96.2

Maximum Start Amps

A

204.0

195.4

200.1

Recommended Mains Fuse Size

A

100

100

125

Unit Data Cooling Only

(2)

Nominal Run Amps

A

46.4

46.6

52.9

Maximum Start Amps

A

160.7

152.1

156.8

Recommended Mains Fuse Size

A

63

63

63

Max Mains Incoming Cable Size

mm²

50

50

50

Mains Supply

V

Mains Supply

Control Circuit

VAC

24

24

24

Evaporator Fan - Per Fan
Maximum Electrical Input Power

(3)

kW

2 x 2.2

2 x 2.2

2 x 3

Full Load Amps

A

4.64

4.64

6.18

Locked Rotor Amps

A

32.5

32.5

43.3

Compressor - Per Compressor
Quantity x Motor Size

kW

2 x 7.8

2 x 8.5

2 x 9.7

Nominal Run Amps

A

15.7

14.5

16.1

Locked Rotor Amps

A

130

120

120

Type of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size

kW

2 x 0.6

3 x 0.6

3 x 0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating

kW

30

30

30

Curent per Phase

A

43.30

43.30

43.30

Humidifier
Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.24

16.24

16.24

73

EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013

Te

ch

nic

al

X-T

yp

e

DF

Technical Data Downflow Units X Type

Electrical Data

Mechanical

(1)

Entering air 24°C/45% RH ambient 35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.