EasiCool™EZE

Precision Air Conditioning

V50WX2 - V60WX2

Technical Data Upflow Units WX Type

Electrical Data

V50WX2-EZE-0

V55WX2-EZE-0

V60WX2-EZE-0

Unit Data Full Function

(1)

Nominal Run Amps

A

87.6

85.2

88.4

Maximum Start Amps

A

201.9

190.7

192.3

Recommended Mains Fuse Size

A

100

100

100

Unit Data Cooling Only

(2)

Nominal Run Amps

A

44.3

41.9

45.1

Maximum Start Amps

A

158.6

147.4

149.0

Recommended Mains Fuse Size

A

50

50

63

Max Mains Incoming Cable Size

mm²

35

35

35

Mains Supply

V

400V / 3PH + N / 50HZ

Control Circuit

VAC

24

24

24

Evaporator Fan - Per Fan
Maximum Electrical Input Power

(3)

kW

2 x 3

2 x 3

2 x 3

Full Load Amps

A

6.18

6.18

6.18

Locked Rotor Amps

A

43.3

43.3

43.3

Compressor - Per Compressor
Quantity x Motor Size

kW

2 x 7.8

2 x 8.5

2 x 9.7

Nominal Run Amps

A

15.7

14.5

16.1

Locked Rotor Amps

A

130

120

120

Type of Start

Direct On Line

Standard Condenser Match - AC Motor - Per Fan
Quantity x Motor Size

kW

2 x 0.6

3 x 0.6

3 x 0.6

Full Load Amps

A

2.62

2.62

2.62

OPTIONAL EXTRAS
Electric Heating
Stage of Reheat

3

3

3

Number of Elements

9

9

9

Rating

kW

30

30

30

Curent per Phase

A

43.30

43.30

43.30

Humidifier
Capacity

kg/hr

15

15

15

Rating

kW

11.25

11.25

11.25

Full Load Amps

A

16.24

16.24

16.24

137

EasiCool™ EZE Technical Manual 7588163 V1.1.0_02_2013

Te

ch

nic

al

W

X - T

yp

e

V

Mechanical

(1)

Entering air 24°C/45% RH condenser water in / out: 30°C/35°C.

(2)

Fan Gain / Fan power input based upon fan operating with design airflow at 25Pa ESP, These values may change with different ESP.

(3)

With Standard forward curved fan motors; Machine weight includes a refrigerant charge /Operating weight includes calculated water volume.

(4)

Backward curved EC fan options quote electrical power. All other options quote shaft power.

(5)

For refrigerant charges, refer to

Unit Refrigerant Charge (kg/Circuit)

.

(6)

Based on air temperature of 15.5°C leaving the evaporator coil.

(7)

Based upon low pressure hot water 82°C inlet / 71°C outlet. Air on 20°C. Refer to

Low Pressure Hot Water (Optional Extra) - X & WX Models

.

Electrical

(1)

Values given for full function units (incl. electric heating, humidification and matched condenser) at 7°C evaporating and 54.4°C condensing with standard

forward curved fan motors, for optional data, please contact Airedale.

(2)

Values given for Cooling only units (incl. Compressor, evaporator fan and matched condenser) at 7°C evaporating and 54.4°C condensing, for optional

data, please contact Airedale.

(3)

Electrical input power relates to the maximum absorbed electrical power. Actual operating fan power input is shown in the mechanical data tables.